SINGLE FAMILY OTHER
Apply Date:
11/30/1999
Applicant:
FAGAN ELECTRIC MAINTENANCE CORP
Description:
UPGRADE:ELECTRIC 100 AMP TO 200 AMP
Contractors:
  • FAGAN ELECTRICAL MAINTENANCE ,

Completed Inspections

Permit Status: Final
Permit Number: T99EL03110
Permit Description: UPGRADE:ELECTRIC 100 AMP TO 200 AMP
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/23/1999 ELECTRIC - SERVICE UPGRADE RSUBA Approved IVRS - Inspection 0999*
12/23/1999 ELECTRIC - SERVICE UPGRADE RSUBA Approved ADDTL COMMS - 1. SECURE CONDUIT AGAIN WHEN YOU INSTALLED YERS HUB YOU FORGOT ABOUT THE ONE HOLE STRAPS(?) 2. BRACE RISER AT SERVICE #2 AS WAS REQUESTED AT PREVIOUS INSPECTION 3. THERE IS A GAP WHERE 3/4 MYERS HUB IS INSTALLED (2 THINGS) SEAL OPENING BETWEEN KNOCKOUT AND MYERS HUB INSTALL GROUNDING CONDUCTOR THROUGH CONDUIT 3/4 AND PROPERLY TERMINATE AT EACH END.