Inspection Status: Correction Required
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/05/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - BRACE RISERS DONE, OK TO CLEAR AND FINAL. |
| 12/23/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - 1. SECURE CONDUIT AGAIN WHEN YOU INSTALLED YERS HUB YOU FORGOT ABOUT THE ONE HOLE STRAPS(?) 2. BRACE RISER AT SERVICE #2 AS WAS REQUESTED AT PREVIOUS INSPECTION 3. THERE IS A GAP WHERE 3/4 MYERS HUB IS INSTALLED (2 THINGS) SEAL OPENING BETWEEN KNOCKOUT AND MYERS HUB INSTALL GROUNDING CONDUCTOR THROUGH CONDUIT 3/4 AND PROPERLY TERMINATE AT EACH END. |
| 12/23/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |
| 12/10/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - INSTALL BONDING BUSHINGS WHERE SEALING LOCKNUTS USED PER ART 250 OR INSTALL GROUNDING CONDUCTOR AND BOND THE OTHER END OF CONDUIT INSTALLATION |
| 12/10/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |
| 12/02/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - 1. PLASTIC ANCHORE NOT SUITABLE FOR SECURING 2 RIGID RISER 2. INSTALL WEATHERPROOF ENTRYS ON TOP OR SERVICE PANEL 3. SECURE CONDUIT PER N.E.C. (E.M.T.) |
| 12/02/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |