Permit: T99EL03110

Parcel: 126172200

Inspection Status: Correction Required

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/05/2000 ELECTRIC - SERVICE UPGRADE Correction Required ADDTL COMMS - BRACE RISERS DONE, OK TO CLEAR AND FINAL.
12/23/1999 ELECTRIC - SERVICE UPGRADE Correction Required ADDTL COMMS - 1. SECURE CONDUIT AGAIN WHEN YOU INSTALLED YERS HUB YOU FORGOT ABOUT THE ONE HOLE STRAPS(?) 2. BRACE RISER AT SERVICE #2 AS WAS REQUESTED AT PREVIOUS INSPECTION 3. THERE IS A GAP WHERE 3/4 MYERS HUB IS INSTALLED (2 THINGS) SEAL OPENING BETWEEN KNOCKOUT AND MYERS HUB INSTALL GROUNDING CONDUCTOR THROUGH CONDUIT 3/4 AND PROPERLY TERMINATE AT EACH END.
12/23/1999 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
12/10/1999 ELECTRIC - SERVICE UPGRADE Correction Required ADDTL COMMS - INSTALL BONDING BUSHINGS WHERE SEALING LOCKNUTS USED PER ART 250 OR INSTALL GROUNDING CONDUCTOR AND BOND THE OTHER END OF CONDUIT INSTALLATION
12/10/1999 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
12/02/1999 ELECTRIC - SERVICE UPGRADE Correction Required ADDTL COMMS - 1. PLASTIC ANCHORE NOT SUITABLE FOR SECURING 2 RIGID RISER 2. INSTALL WEATHERPROOF ENTRYS ON TOP OR SERVICE PANEL 3. SECURE CONDUIT PER N.E.C. (E.M.T.)
12/02/1999 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*