Status:
Closed
Type:
COMMERCIAL ADDITION
Address:
727 E EVANS BL
Address NEW:
727 E EVANS BL
Apply Date:
11/18/1999
Applicant:
FAGIN, EDWARD A
Description:
ADDITION:OFFICE
Architects:
  • FAGIN, EDWARD A
Contractors:
  • BLUELINE CONSTRUCTION INC

Outstanding Inspections

Permit Status: Closed
Permit Number: T99CM05497
Permite Description: ADDITION:OFFICE
Total Outstanding Inspections - 20
Last Inspection Date Description Inspector Results Comments
EXCAVATION/LAYOUT REBAR & ZON N/A Not Inspected
STEM WALL/RETAINING WALL N/A Not Inspected
REINFORCED MASONRY PRE-GROUT N/A Not Inspected
EXT METAL CLIPS/EXT SHEATHING N/A Not Inspected
BUILDING - FINAL N/A Not Inspected
ELECTRIC - ABOVE CEILING N/A Not Inspected
PLUMBING - ABOVE CEILING N/A Not Inspected
PLUMBING - YARD WTR LINE/TEST N/A Not Inspected
PLUMBING - PROGRESS N/A Not Inspected
MECHANICAL - ABOVE CEILING N/A Not Inspected
MECHANICAL - PROGRESS N/A Not Inspected
FIRE - FINAL N/A Not Inspected
LANDSCAPE - FINAL N/A Not Inspected
SIGN - FINAL N/A Not Inspected
06/15/2000 MECHANICAL - INTERMEDIATE N/A Correction Required ADDTL COMMS - 1. CONDENSATE DRAIN RUNS UPHILL NEED 1/8 PER FOOT MIN SLOPE. 2. CONDENSATE DRAIN CORRECTION TO AIR HANDLER IS CONNECTED TO THE WRONG OUTLET USE THREADED PLUGS IN OUTLETS NOT BEING USED. 3. INSULATE REFER LINE ALL THE WAY TO THE UNIT. 4. FINISH DUCT ON EXHAUST FANS 5. INSTALL OUTSIDE AIR TO UNIT. SPACE HAS NO OPENABLE WINDOWS. RECALL WHEN GRID IS INSTALLED AND DIFFUSERS HOOKED UP
06/20/2000 ELECTRIC - INTERMEDIATE N/A Correction Required ADDTL COMMS - WALLS FROM COLUMN B TO WEST
06/22/2000 PLUMBING - INTERMEDIATE N/A Correction Required ADDTL COMMS - 1. NEED A 2 STUB OUT OF WALL A SINK REMOVE 1 1/2 2. SUPPORT H & C WATER LINES 3. QUEST ABS WATER TEST- CUT VENT TO SEE WATER 4. CHECK W.C.O P-7
08/07/2000 ELECTRIC - FINAL N/A Partial Approval PLEASE HAVE APPROVED PLANS AVAILABLE AND WILL NEED TO SCREW DOWN FIXTURE TO GRID W/TABS AND SCREWS PROVIDE W/ FIXTURE
08/07/2000 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection 0000*
REFRIG LINES BE SURE 3/8" COPPER LINE IS COMPLETELY ISOLATED FROM TOUCHING ALL STEEL
2. SUPPLY DUCT WK FINISH WRAPING GALVAN STEEL FITTING OVER STEEL I BEAM GOING TO NEW REST RMS
AIR HANDLER DATA PLATE NOT MARKED DOES A/H HAVE AUX HT STRIPS YES WHAT SIZE
NO ? DID YOU HAVE IT PROPERLY FUSED
EXPOSED CONTROL WIRING AT CONDENSING UNIT NEEDS TO BE IN SEAL TIGHT
08/29/2000 PLUMBING - FINAL N/A Denied IVRS - Inspection 0999*

Completed Inspections

Permit Status: Closed
Permit Number: T99CM05497
Permit Description: ADDITION:OFFICE
Total Completed Inspections - 1
Date Description Inspector Results Comments
03/29/2000 PLUMBING - ROUGH, SOIL TVALENCI Approved ADDTL COMMS - WILL NEED AS BUILTS ON UNDER GROUND WASTE (BEFORE FINAL)