Inspection Status: Correction Required
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/15/2000 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. CONDENSATE DRAIN RUNS UPHILL NEED 1/8 PER FOOT MIN SLOPE. 2. CONDENSATE DRAIN CORRECTION TO AIR HANDLER IS CONNECTED TO THE WRONG OUTLET USE THREADED PLUGS IN OUTLETS NOT BEING USED. 3. INSULATE REFER LINE ALL THE WAY TO THE UNIT. 4. FINISH DUCT ON EXHAUST FANS 5. INSTALL OUTSIDE AIR TO UNIT. SPACE HAS NO OPENABLE WINDOWS. RECALL WHEN GRID IS INSTALLED AND DIFFUSERS HOOKED UP |
| 06/15/2000 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |