Permit: T99CM05312
Permit Details
Apply Date:
11/05/1999
Applicant:
ADVANCE AIR CLEANING AMERICAN AI
Description:
AIR COND:REPLACEMENT
Contractors:
- ADVANCE AIR CLEANING AMERICAN AI
Outstanding Inspections
Permit Status: Expired
Permit Number: T99CM05312
Permite Description: AIR COND:REPLACEMENT
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2000 | MECHANICAL - FINAL | N/A | Correction Required | ADDTL COMMS - MECH FINAL MECH CONTRACTOR PURCHASED PERMIT DID NOT CALL FOR INSPECTION THE FOLLOWING ITEMS NEED TO BE CONNECTED 1. 1/2 RIDGID GAS LINE NEEDS TO BE BLOCKED AND CLAMPED 2. FLEX GAS LINE USED 3/8 X 30 TABKE 3D-2 RATES GOOD FOR 44,000 BTU 3. ELECTRICAL EMT CONNECTOR AT BOTTOM OF HI VOLTAGE SWITCH IS BLOCKING CLOSURE OF SWITCH LID 4. MAX FUSE SIZE 30 AMPS PER UNIT DATA PLATE 35 AMP FUSES IN SWITCH 5. CONDENSATE DRAIN TERMINATE INTO 2 MIN VENT PIPE W/ 3/4 TEE. PAINT PVC PIPE |