Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - MECH FINAL MECH CONTRACTOR PURCHASED PERMIT DID NOT CALL FOR INSPECTION THE FOLLOWING ITEMS NEED TO BE CONNECTED 1. 1/2 RIDGID GAS LINE NEEDS TO BE BLOCKED AND CLAMPED 2. FLEX GAS LINE USED 3/8 X 30 TABKE 3D-2 RATES GOOD FOR 44,000 BTU 3. ELECTRICAL EMT CONNECTOR AT BOTTOM OF HI VOLTAGE SWITCH IS BLOCKING CLOSURE OF SWITCH LID 4. MAX FUSE SIZE 30 AMPS PER UNIT DATA PLATE 35 AMP FUSES IN SWITCH 5. CONDENSATE DRAIN TERMINATE INTO 2 MIN VENT PIPE W/ 3/4 TEE. PAINT PVC PIPE |