Permit: T99CM04911
Permit Details
Apply Date:
10/18/1999
Applicant:
FLORES JOSE REYES & RAMONA JT/RS
Description:
ADDITION:SHED T99VL01326
Completed Inspections
Permit Status: Final
Permit Number: T99CM04911
Permit Description: ADDITION:SHED T99VL01326
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/1999 | PERMIT FINALED | JRIVA | Approved | |
| 12/13/1999 | ELECTRIC - FINAL | JRIVA | Approved | IVRS - Inspection 0999* |
| 12/13/1999 | BUILDING - FINAL | JRIVA | Approved | IVRS - Inspection 0999* |
| 12/13/1999 | BUILDING - FINAL | JRIVA | Approved | ADDTL COMMS - RIDGE BEAM MUST BEAR ON POST ON N WALL OR CLIP PER 1/1. INSTALL H2.5 CLIPS ON ALL 2 X 6 RAFTERS. 5 FEET OF INSIDE STORAGE BACK E WALL MUST HAVE 5/8 DRYWALL. STRAP EAST TOPO PLATE TO STUDS BELOW. WIRES MUST EXTEND INTO ELECTRIC BOXES. EXPOSE ELECTRIC UNDERGROUND IN ONE LOCATION. OUTSIDE ELECTRIC OUTLETS MUSTS BE GFIC. INSIDE ELECTRIC OUTLETS MUST BE GFIC OR WALLS FINISHED. ELECTRIC PLAN SHOWS SINGLE 20 AMP CIRCUIT FOR LIGHTS AND ONE OUTLET ACTUALLY 50 AMP INSTALLED. NEED SUB-PANEL AND PLANS REVISED TO AS BUILT |
| 12/13/1999 | FRAMING | JRIVA | Approved | IVRS - Inspection 0999* |
| 12/13/1999 | EXT METAL CLIPS/EXT SHEATHING | JRIVA | Approved | IVRS - Inspection 0999* |