Permit: T99CM01542
Permit Details
Status:
Final
Type:
SINGLE FAMILY ADDITION
Address:
1941 W TOURNEY RD
Address NEW:
1941 W TOURNEY RD
Apply Date:
04/06/1999
Applicant:
WILLIAMS TROY
Description:
ADDITION:ARIZONA ROOM/ENCLOSURE:CARPORT TO DEN
Completed Inspections
Permit Status: Final
Permit Number: T99CM01542
Permit Description: ADDITION:ARIZONA ROOM/ENCLOSURE:CARPORT TO DEN
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/1999 | ELECTRIC - TEMPORARY SERVICE | RAIELLO | Approved | ADDTL COMMS - 1. REBAR LAYOUT 741-3000 GUS 882-9467 RES 2. TROY- TEMP POWER |
| 11/13/2000 | FRAMING | RAIELLO | Approved | IVRS - Inspection 0000* |
| 11/08/2001 | MECHANICAL - FINAL | DBRITO | Approved | IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION |
| 10/17/2003 | PLUMBING - FINAL | JRIVA | Approved | IVRS - Inspection 0000* |
| 10/01/2004 | ELECTRIC - FINAL | JRIVA | Approved | IVRS - Inspection : See detailed listing on site.| 999*/ 1) OUTLET LEFT OFF OVEN MUST BE GFCI PROTECTED 2) PENINSULA OUTLETS MUST BE GFCI PROTECTED 3) ALL KITCHEN COUNTER OUTLETS MUST BE GFCI PORTECTED 4) CIRCUIT BREAKERS 32, 34 AND 36 HAVE #14 WIRE ON 20 AMP BREAKERS CHANGE TO MPT 15 AMP BREAKERS 5) LABEL ALL CIRCUITS IN SUB-PANEL 6) ONE BATH OUTLET NOT GFCI |
| 03/27/2006 | BUILDING - FINAL | EDURAZO | Approved | IVRS - Inspection :* |
| 09/26/2006 | PERMIT FINALED | LJACKSON | Approved |