Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE LAST INSPE |
|
| 10/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) OUTLET LEFT OFF OVEN MUST BE GFCI PROTECTED 2) PENINSULA OUTLETS MUST BE GFCI PROTECTED 3) ALL KITCHEN COUNTER OUTLETS MUST BE GFCI PORTECTED 4) CIRCUIT BREAKERS 32, 34 AND 36 HAVE #14 WIRE ON 20 AMP BREAKERS CHANGE TO MPT 15 AMP BREAKERS 5) LABEL ALL CIRCUITS IN SUB-PANEL 6) ONE BATH OUTLET NOT GFCI |
|
| 04/08/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |