Permit: T99CM00500
Permit Details
Status:
Final
Type:
MULTI FAMILY ALTERATION
Address:
7671 E TANQUE VERDE RD
Address NEW:
7671 E TANQUE VERDE RD
Apply Date:
02/05/1999
Applicant:
CARRIER CORPORATION ,
Description:
TI:APARTMENT MECHANICAL ROOM
Contractors:
- CARRIER CORPORATION ,
Completed Inspections
Permit Status: Final
Permit Number: T99CM00500
Permit Description: TI:APARTMENT MECHANICAL ROOM
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/1999 | PLUMBING - PROGRESS | TRINIVJR | Approved | ADDTL COMMS - 1. GAS PRESSURE TEST O.K. 2. GAS PIPING TO METER O.K. 3. GAS CLEARANCE CARD ISSURED BY BOILER INSPECTOR. |
| 12/15/1999 | PLUMBING - GAS PRESSURE TEST | TRINIVJR | Approved | ADDTL COMMS - 1. GAS PRESSURE TEST O.K. 60 LBS 2. GAS PIPING TO METER O.K. 3. GAS CLEARANCE CARD ISSUED BY BOILER INSPECTOR. |
| 12/15/1999 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | ADDTL COMMS - 12/14/99 EXHAUST FAN NORTA SIDE 1. PROVIDE CLEARANCE IN FRONT OF DISCONNECT OUT 3 2. LABEL DISCONNECT BOILER 1. PERMANENTLY LABEL DISCONNECT AT SWITCH GEAR 2. INSTALL FUSE REDUCERS 3. CLEAR IN FRONT OFF CONTROL PNL AT BOILER ONLY 30 WILL NEED 36 APPEAL OR RELOCATE 4. PERMANENTLY LABEL DISCON AND STARTER TO HOT WATER AIR PUMP. |