Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/15/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 12/14/99 EXHAUST FAN NORTA SIDE 1. PROVIDE CLEARANCE IN FRONT OF DISCONNECT OUT 3 2. LABEL DISCONNECT BOILER 1. PERMANENTLY LABEL DISCONNECT AT SWITCH GEAR 2. INSTALL FUSE REDUCERS 3. CLEAR IN FRONT OFF CONTROL PNL AT BOILER ONLY 30 WILL NEED 36 APPEAL OR RELOCATE 4. PERMANENTLY LABEL DISCON AND STARTER TO HOT WATER AIR PUMP. |
| 11/22/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - NOT READY PLEASE NOTE ALL ELEC EQUPMENT PANELS AND SECTION TO HAVE 36 CLEAR IN FRONT OF THEM EXIST PRE 78 CODE UNSTALLS NEEDED 30 |
| 11/22/1999 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |