Permit: T99CM00264
Permit Details
Status:
Expired
Type:
SINGLE FAMILY ALTERATION
Address:
1404 N BRYANT AV
Address NEW:
1404 N BRYANT AV
Apply Date:
01/21/1999
Applicant:
BETTERWAY SERVICES INC ,
Description:
REPAIR:FIRE DAMAGE
Contractors:
- BETTERWAY SERVICES INC ,
Outstanding Inspections
Permit Status: Expired
Permit Number: T99CM00264
Permite Description: REPAIR:FIRE DAMAGE
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PERMIT FINALED | N/A | Not Inspected | ||
| 02/19/1999 | MECHANICAL - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection 0000* |
| 05/25/1999 | BUILDING - FINAL | N/A | Correction Required | ADDTL COMMS - INSTALL SMOKE DETECTORS: WALL INSTALLATION: MINIMUM 6 MAXIMUM 12 BELOW CEILING. MINIMUM 18 FROM ANY CORNER CEILING INSTALLATION: MINIMUM 6 FROM ANY CERTICAL SURFACE INSTALLATION SHALL BE A MINIMUM OF 3 FEET FROM ANY MECHANICAL SUPPLY OR RETURN GRILL. LIVING ROOM- LESS THAN 6 AND LESS THAN 3 FROM GRILL HALL- OKAY BEDROOM- LESS THAN 3 FROM GRILL. |