Inspection Status: Correction Required
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/25/1999 |
BUILDING - FINAL |
|
Correction Required |
ADDTL COMMS - INSTALL SMOKE DETECTORS: WALL INSTALLATION: MINIMUM 6 MAXIMUM 12 BELOW CEILING. MINIMUM 18 FROM ANY CORNER CEILING INSTALLATION: MINIMUM 6 FROM ANY CERTICAL SURFACE INSTALLATION SHALL BE A MINIMUM OF 3 FEET FROM ANY MECHANICAL SUPPLY OR RETURN GRILL. LIVING ROOM- LESS THAN 6 AND LESS THAN 3 FROM GRILL HALL- OKAY BEDROOM- LESS THAN 3 FROM GRILL. |
| 05/25/1999 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999* |