Permit: T98CM03008
Permit Details
Apply Date:
07/13/1998
Applicant:
FARNEY WILLIAM C & RAFAELA JT/RS
Description:
REMODEL:GARAGE TO FAMILY ROOM & ADDITION:GARAGE
Outstanding Inspections
Permit Status: Expired
Permit Number: T98CM03008
Permite Description: REMODEL:GARAGE TO FAMILY ROOM & ADDITION:GARAGE
Total Outstanding Inspections - 9
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| BUILDING - FINAL | N/A | Not Inspected | ||
| ELECTRIC - FINAL | N/A | Not Inspected | ||
| PLUMBING - INTERMEDIATE | N/A | Not Inspected | ||
| PLUMBING - FINAL | N/A | Not Inspected | ||
| MECHANICAL - INTERMEDIATE | N/A | Not Inspected | ||
| MECHANICAL - FINAL | N/A | Not Inspected | ||
| PERMIT FINALED | N/A | Not Inspected | ||
| 12/31/1998 | FRAMING | N/A | Correction Required | ADDTL COMMS - 1. WILL NEED SOME TYPE OF SADDLE, OR STRAP FOR GLU-LAM BEAM ON C.M.U WALL. 2. OKAY TO COVER CONDUIT FROM SERV TO GARAGE. 3. SUB-PANEL IN GARAGE NEEDS A GRD BUSS INSTALLED ISOLATE NEUTRALS/GRDS IF NO GRD ELECTRODE TO BE INSTALLED WILL NEED A 4 WIRE FEEDER. 4. STRAP ALL POSTS TO CORBELS BEAMS. 5. FRAMING FOR HOBBY OKAY. 6. NEED MECH INSPECTION, POWER SOURCE FOR H/P AND DUCTING OR VAPOR LINES TO H/P UNIT INSIDE CHECK WITH PERSON DOING WORK. |
| 12/31/1998 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | OK TO INSULATE |