Permit Details

Status:
Final
Type:
SINGLE FAMILY ADDITION
Apply Date:
12/12/1997
Applicant:
G & S SALES
Description:
GARAGE:TD#13-94-74
Contractors:
  • CALIBER WEST L L C

Completed Inspections

Permit Status: Final
Permit Number: T97CM04053
Permit Description: GARAGE:TD#13-94-74
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/15/1997 FRAMING JRIVA Approved DENIED
12/15/1997 ROOF NAILING JRIVA Approved DENIED
12/15/1997 ROOF NAILING JRIVA Approved ADDTL COMMS - 1. ROOF COVERED W/OUT INSP. REMOVE SQUARE OF SHINGLES TO VERIFY SHEATHING INSTALLATION. 2. INSTALLED TRUSSES DONOT MATCH TRUSS DRAWINGS. DRAWING IS 20 SPAN TRUSS, INSTALLED IS 26 SPAN. 3. CONCRETE SLAB POURED W/OUT INSPECTION. PROVIDE PROOF OF SLAB FTG WIDTH, DEPTH AND INSTALLED STEEL. 4. ANCHOR BOLTS REQ W/IN 12 OF SILL PLATE ENDS AND SPLICES. 5. EXT SHEATHING COVERED W/OUT INSP. NOT PROPERLY FASTENED TO STUDS. PROVIDE ICBO REPORT FOR COATING APPLIED AS EXT FINISH. 6. DAY WALL FIRE SEPARATION NOT PER PLAN-REQ 5/8 TYPE X 2 LAYERS. 7. BATHRM WINDOW INTO GARAGE NOT FIRE RATED. NOTE- THESE GARAGE ADDITIONS ARE BEING ADDED TO MOBILE HOME DURING SETTING OF MH. THIS WILL BE ON EVERY UNIT IN THIS DEVELOPMENT OF 73 LOTS.