Inspection Status: Correction Required

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
12/15/1997 ROOF NAILING Correction Required ADDTL COMMS - 1. ROOF COVERED W/OUT INSP. REMOVE SQUARE OF SHINGLES TO VERIFY SHEATHING INSTALLATION. 2. INSTALLED TRUSSES DONOT MATCH TRUSS DRAWINGS. DRAWING IS 20 SPAN TRUSS, INSTALLED IS 26 SPAN. 3. CONCRETE SLAB POURED W/OUT INSPECTION. PROVIDE PROOF OF SLAB FTG WIDTH, DEPTH AND INSTALLED STEEL. 4. ANCHOR BOLTS REQ W/IN 12 OF SILL PLATE ENDS AND SPLICES. 5. EXT SHEATHING COVERED W/OUT INSP. NOT PROPERLY FASTENED TO STUDS. PROVIDE ICBO REPORT FOR COATING APPLIED AS EXT FINISH. 6. DAY WALL FIRE SEPARATION NOT PER PLAN-REQ 5/8 TYPE X 2 LAYERS. 7. BATHRM WINDOW INTO GARAGE NOT FIRE RATED. NOTE- THESE GARAGE ADDITIONS ARE BEING ADDED TO MOBILE HOME DURING SETTING OF MH. THIS WILL BE ON EVERY UNIT IN THIS DEVELOPMENT OF 73 LOTS.
12/15/1997 ROOF NAILING Denied DENIED