Date Description Inspector Results Comments
10/02/2008 PERMIT FINALED CFUNKE Approved
10/02/2008 FUEL TANK FINAL 791-4502 CFUNKE Approved The 3,000 gallon double wall AST (1000/2000 split) was installed in 11/97. The tank is sub-grade in a open concrete vault with a sump system to remove rain water. Fire extinguishers, tank vents, dispensing nozzles, overfill prevention and the emergency stop are approved. A permit has been issued.