Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FUEL TANK FINAL 791-4502
Permit Number - T97BU02248
Inspection Description - FUEL TANK FINAL 791-4502
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2008 | FUEL TANK FINAL 791-4502 | Approved | The 3,000 gallon double wall AST (1000/2000 split) was installed in 11/97. The tank is sub-grade in a open concrete vault with a sump system to remove rain water. Fire extinguishers, tank vents, dispensing nozzles, overfill prevention and the emergency stop are approved. A permit has been issued. |