Permit: T22FO00205
Permit Details
Apply Date:
03/02/2022
Applicant:
Description:
High-Piled Storage - Installation of storage racks into an existing building.; Other Operational Permit
Completed Inspections
Permit Status: Complete
Permit Number: T22FO00205
Permit Description: High-Piled Storage - Installation of storage racks into an existing building.; Other Operational Permit
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2022 | COT - FCOD - Fire Operational Permit | Passed | {Activity date: 03/09/2022; Status: Prior to Final Inspectn; Inspector: JPEEL-DAVIS; Comment: Entered by JPEELDA1 - Confirm that there are smoke vents in 15' perimeter of high piled storage confirm that they have fusible links that are 360 deg minimimum installed check table 3206.2 esfr shall not be used in buildings with automatic heat or smoke vents unless the vents use a standard-rsponse operating mechnaism withi a minimum temperature rating of 360 deg or 100 deg f above the operating temperature of the sprinklers, whichever is higher.} |