Permit Details

Status:
Complete
Type:
Fire Operational Permit
Apply Date:
03/02/2022
Applicant:
Description:
High-Piled Storage - Installation of storage racks into an existing building.; Other Operational Permit

Completed Inspections

Permit Status: Complete
Permit Number: T22FO00205
Permit Description: High-Piled Storage - Installation of storage racks into an existing building.; Other Operational Permit
Total Completed Inspections - 1
Date Description Inspector Results Comments
03/09/2022 COT - FCOD - Fire Operational Permit Passed {Activity date: 03/09/2022; Status: Prior to Final Inspectn; Inspector: JPEEL-DAVIS; Comment: Entered by JPEELDA1 - Confirm that there are smoke vents in 15' perimeter of high piled storage
confirm that they have fusible links that are 360 deg minimimum installed
check table 3206.2 esfr shall not be used in buildings with automatic heat or smoke vents unless the vents use a standard-rsponse operating mechnaism withi a minimum temperature rating of 360 deg or 100 deg f above the operating temperature of the sprinklers, whichever is higher.}