Permit: T22FO00205

Parcel: 14041134D


Addresses:

7000 S ALVERNON WY


Inspection Status: Passed

Inspection History: COT - FCOD - Fire Operational Permit

Permit Number - T22FO00205

Inspection Description - COT - FCOD - Fire Operational Permit

Inspection Status - Passed

Date Description Inspector Results Comments
03/09/2022 COT - FCOD - Fire Operational Permit JPEEL-DAVIS Prior to Final Inspectn Entered by JPEELDA1 - Confirm that there are smoke vents in 15' perimeter of high piled storage confirm that they have fusible links that are 360 deg minimimum installed check table 3206.2 esfr shall not be used in buildings with automatic heat or smoke vents unless the vents use a standard-rsponse operating mechnaism withi a minimum temperature rating of 360 deg or 100 deg f above the operating temperature of the sprinklers, whichever is higher.