Inspection History Details
Inspection Status: Passed
Inspection History: COT - FCOD - Fire Operational Permit
Permit Number - T22FO00205
Inspection Description - COT - FCOD - Fire Operational Permit
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2022 | COT - FCOD - Fire Operational Permit | JPEEL-DAVIS | Prior to Final Inspectn | Entered by JPEELDA1 - Confirm that there are smoke vents in 15' perimeter of high piled storage confirm that they have fusible links that are 360 deg minimimum installed check table 3206.2 esfr shall not be used in buildings with automatic heat or smoke vents unless the vents use a standard-rsponse operating mechnaism withi a minimum temperature rating of 360 deg or 100 deg f above the operating temperature of the sprinklers, whichever is higher. |