Permit Details

Status:
Complete
Type:
Fire Construction Permit
Address NEW:
1102 E 36TH ST BLDG 1
Apply Date:
07/13/2022
Applicant:
Description:
Automatic Fire Extingshing Sys - New Wood Construction- Apartments 4- Three story buildings.; Additional Inspections: 1

Outstanding Inspections

Permit Status: Complete
Permit Number: T22FC00462
Permite Description: Automatic Fire Extingshing Sys - New Wood Construction- Apartments 4- Three story buildings.; Additional Inspections: 1
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
10/26/2022 COT - FCON - Sprinkler - Final N/A Not Ready

Completed Inspections

Permit Status: Complete
Permit Number: T22FC00462
Permit Description: Automatic Fire Extingshing Sys - New Wood Construction- Apartments 4- Three story buildings.; Additional Inspections: 1
Total Completed Inspections - 2
Date Description Inspector Results Comments
10/20/2022 FCON – OH Piping & Hydro Passed {Activity date: 10/20/2022; Status: Approved; Inspector: CGates; Comment: Entered by CGATES1 - } ; {Activity date: 09/20/2022; Status: Partial Approval; Inspector: CGates; Comment: Entered by CGATES1 - 1st Floor:220 psi. East/south 2b water heater closet heat blocked, east/north 1b head in ac closet blocked. south/east studio missing head in laundry area
2nd Floor: 220 psi. noth/east studio wrong upright, west/south 2b wrong upright, south east/west 1b wrong upright
3rd Floor: 220 psi.
Amenity Building not inspected.
}
09/22/2023 COT - FCON - Sprinkler - Final Passed