Inspection Status: Passed
Inspection History: FCON – OH Piping & Hydro
| Date |
Description |
Inspector |
Results |
Comments |
| 10/20/2022 |
FCON – OH Piping & Hydro |
CGates |
Approved |
Entered by CGATES1 - |
| 09/20/2022 |
FCON – OH Piping & Hydro |
CGates |
Partial Approval |
Entered by CGATES1 - 1st Floor:220 psi. East/south 2b water heater closet heat blocked, east/north 1b head in ac closet blocked. south/east studio missing head in laundry area
2nd Floor: 220 psi. noth/east studio wrong upright, west/south 2b wrong upright, south east/west 1b wrong upright
3rd Floor: 220 psi.
Amenity Building not inspected.
|