Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
Residential Building - One or Two Family
Address NEW:
8440 E VICKSBURG ST
Apply Date:
01/10/2022
Applicant:
Hector Rubio
Description:
Panel upgrade to 200 amps.

Outstanding Inspections

Permit Status: Expired
Permit Number: T22CM00160
Permite Description: Panel upgrade to 200 amps.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
11/07/2022 COT - RSEL - Electrical Final N/A Canceled Inspection Canceled

Completed Inspections

Permit Status: Expired
Permit Number: T22CM00160
Permit Description: Panel upgrade to 200 amps.
Total Completed Inspections - 2
Date Description Inspector Results Comments
02/02/2022 PDSD Building Division - TEP PM Clearance Passed {Activity date: 02/02/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - CODE INCR}
02/02/2022 COT - RSEL - Service Upgrade Passed {Activity date: 02/02/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP INCR clearance code for TEP. Phoned in at 8:54} ; {Activity date: 02/01/2022; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - CO
GEC is a #6 and table 3603.4 requires a #4 CU for a 4/0 AL ungrounded service entrance conductor.}

Documents

File Name Document Type  
PERMIT.PDF DOCUMENTS VIEW
APPLICATION.PDF DOCUMENTS VIEW
JOB CARD.PDF DOCUMENTS VIEW