Permit: T22CM00160
Permit Details
Status:
Expired
Type:
Residential Building - One or Two Family
Address:
8440 E VICKSBURG ST
Address NEW:
8440 E VICKSBURG ST
Apply Date:
01/10/2022
Applicant:
Hector Rubio
Description:
Panel upgrade to 200 amps.
Outstanding Inspections
Permit Status: Expired
Permit Number: T22CM00160
Permite Description: Panel upgrade to 200 amps.
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2022 | COT - RSEL - Electrical Final | N/A | Canceled | Inspection Canceled |
Completed Inspections
Permit Status: Expired
Permit Number: T22CM00160
Permit Description: Panel upgrade to 200 amps.
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2022 | PDSD Building Division - TEP PMÂ Clearance | Passed | {Activity date: 02/02/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - CODE INCR} | |
| 02/02/2022 | COT - RSEL - Service Upgrade | Passed | {Activity date: 02/02/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP INCR clearance code for TEP. Phoned in at 8:54} ; {Activity date: 02/01/2022; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - CO GEC is a #6 and table 3603.4 requires a #4 CU for a 4/0 AL ungrounded service entrance conductor.} |