Inspection Status: Passed
Inspection History: COT - RSEL - Service UpgradeĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 02/02/2022 |
COT - RSEL - Service UpgradeĀ |
RCHANDLER |
Approved |
Entered by NGARCIA3 - AP INCR clearance code for TEP. Phoned in at 8:54 |
| 02/01/2022 |
COT - RSEL - Service UpgradeĀ |
TLUNDBERG |
Correction Required |
Entered by VVERA1 - CO
GEC is a #6 and table 3603.4 requires a #4 CU for a 4/0 AL ungrounded service entrance conductor. |