Permit Details

Status:
Complete
Type:
Commercial Building
Apply Date:
12/17/2021
Applicant:
Description:
Health Clinic

Permit Reviews

Permit Number - T21CM09661
Permit Status: Complete
Permit Description: Health Clinic
Start Date Submittal Complete Date Status  
02/11/2022 RESUBMITTAL 03/10/2022 COMPLETED Review Details
03/10/2022 RESUBMITTAL 03/21/2022 COMPLETED Review Details
04/01/2022 RESUBMITTAL 04/12/2022 COMPLETED Review Details
12/17/2021 COMMERCIAL - BLDG/FIRE/ZONING/ENG 02/02/2022 COMPLETED Review Details
11/17/2022 COMMERCIAL REVIEW - FULL v.1 11/18/2022 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - T21CM09661
Permit Status: Complete
Permit Description: Health Clinic
Total Outstanding Activity Conditions - 1
Date Name
11/30/2022 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit.

Conditions

Permit Number - T21CM09661
Permit Status: Complete
Permit Description: Health Clinic
Date Description Comments
04/12/2022 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
04/12/2022 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
04/12/2022 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
04/12/2022 SHOP DRAWINGS REQUIRED FOR SPRINKLERS.
09/29/2022 WATER CHLORINATION REPORT REQUIRED

Outstanding Inspections

Permit Status: Complete
Permit Number: T21CM09661
Permite Description: Health Clinic
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
10/04/2022 COT - LCPL - Plumbing Intermediate N/A Canceled {Activity date: 10/04/2022; Status: Not Applicable; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - N/A} ; {Activity date: 06/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved. Southwest gas clearance is required.

} ; {Activity date: 06/10/2022; Status: Cancelled; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Canceled by contractor, Jim

} ; {Activity date: 04/20/2022; Status: Partial Approval; Inspector: DQUINN; Comment: Entered by NGARCIA3 - pa
All under slab rough plumbing ok to backfill.}
10/04/2022 COT - LCME - Mechanical Intermediate N/A Canceled {Activity date: 10/04/2022; Status: Not Applicable; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - N/A} ; {Activity date: 08/24/2022; Status: Partial Approval; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Partial approval Seismic missing on some diffusers

} ; {Activity date: 06/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved. Southwest gas clearance is required.

} ; {Activity date: 06/10/2022; Status: Cancelled; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Canceled by contractor, Jim

}
10/04/2022 COT - LCBU - Building Progress N/A Canceled {Activity date: 10/04/2022; Status: Not Applicable; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - N/A}
11/04/2022 COT - LCPL - Plumbing Progress N/A Canceled Inspection Canceled
11/04/2022 COT - LCME - Mechanical Progress N/A Canceled Inspection Canceled

Completed Inspections

Permit Status: Complete
Permit Number: T21CM09661
Permit Description: Health Clinic
Total Completed Inspections - 19
Date Description Inspector Results Comments
04/20/2022 COT - LCEL - Electrical Progress Passed {Activity date: 04/20/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by NGARCIA3 - Ap}
05/09/2022 COT - LCME - Mechanical Final Passed {Activity date: 05/09/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by VVERA1 - Ap
All duct work ok to be wrapped.} ; {Activity date: 04/12/2022; Status: Prior to Final Inspectn; Inspector: DBENOIT; Comment: Entered by DBENOIT1 - AIR BALANCE REPORT REQUIRED PRIOR TO FINAL INSPECTION}
05/12/2022 COT - LCPL - Plumbing Above Ceiling Passed {Activity date: 05/12/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by VVERA1 - Ap
Potable and dwv ok above.}
06/14/2022 COT - LCPL - Gas Pressure Test Passed {Activity date: 06/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved. Southwest gas clearance is required.

}
06/14/2022 COT - LCEL - Electrical Intermediate Passed {Activity date: 06/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved. Southwest gas clearance is required.

} ; {Activity date: 06/10/2022; Status: Cancelled; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Canceled by contractor, Jim

} ; {Activity date: 06/06/2022; Status: Partial Approval; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Partial approval ok to one side interior walls only

} ; {Activity date: 04/20/2022; Status: Partial Approval; Inspector: DQUINN; Comment: Entered by NGARCIA3 - pa
Under slab conduits ok}
06/14/2022 COT - LCBU - Framing Passed {Activity date: 06/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved. Southwest gas clearance is required.

} ; {Activity date: 06/10/2022; Status: Cancelled; Inspector: ESTEVENS; Comment: Entered by VVERA1 - Canceled by contractor, Jim

}
06/14/2022 COT - BULD - SWG Clearance Passed {Activity date: 06/14/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - CODE GAS}
06/27/2022 COT - HCBU - Interior Shear Bracing Passed {Activity date: 06/27/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by NGARCIA3 - Ap}
08/26/2022 COT - LCME - Mechanical Above Ceiling Passed {Activity date: 08/26/2022; Status: Approved; Inspector: WGALLAGHER; Comment: Entered by NGARCIA3 - Approved}
09/26/2022 COT - FCON - Fire - Final Passed {Activity date: 09/26/2022; Status: Approved; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - }
09/30/2022 COT - LCPL - Plumbing Final Passed {Activity date: 09/30/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by VVERA1 - Ap} ; {Activity date: 09/29/2022; Status: Partial Approval; Inspector: RSHERRY; Comment: Entered by RSHERRY1 - REVIEW OF WATER DISINFECTION REPORT COMPLETED} ; {Activity date: 09/27/2022; Status: Cancelled; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Canceled by contractor} ; {Activity date: 09/21/2022; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Not ready

} ; {Activity date: 07/12/2022; Status: Cancelled; Inspector: DQUINN; Comment: Entered by NGARCIA3 - ca
Per contractor} ; {Activity date: 04/12/2022; Status: Prior to Final Inspectn; Inspector: DBENOIT; Comment: Entered by DBENOIT1 - WATER CHLORINATION REPORT REQUIRED PRIOR TO FINAL INSPECTION}
10/04/2022 COT - LCBU - Building Above Ceiling Passed {Activity date: 10/04/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved} ; {Activity date: 09/21/2022; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Not ready

} ; {Activity date: 08/24/2022; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Not ready
}
10/04/2022 COT - LCEL - Electrical Above Ceiling Passed {Activity date: 10/04/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved} ; {Activity date: 08/24/2022; Status: Partial Approval; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Partial approval awaiting relocation of sub panel
}
10/06/2022 PDSD Building Division - TEP PM Clearance Passed {Activity date: 10/06/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by NGARCIA3 - CODE REC} ; {Activity date: 10/06/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by NGARCIA3 - CODE INCR}
11/03/2022 COT - HCEL - Electrical Progress Passed 400amp service box has been installed, labeled and scheduled.
11/03/2022 COT - LCEL - Electrical Final Passed Please call James Ericson 385-910-4874
11/07/2022 COT - LCEL - Service Upgrade Passed {Activity date: 10/06/2022; Status: Partial Approval; Inspector: DQUINN; Comment: Entered by NGARCIA3 - pa

Clear incr/rec

This is a partial inc, meter power kill, just to pull new feeders to back ordered 400 amp panel.} ; {Activity date: 09/30/2022; Status: Not ready for Inspection; Inspector: DQUINN; Comment: Entered by VVERA1 - nr
Panel on back order till end of oct.
}
11/08/2022 COT - LCBU - Building Final Passed
11/10/2022 ENGR Engineering Final Passed