Permit Details

Status:
Issued
Type:
Residential Building - One or Two Family
Apply Date:
11/08/2021
Applicant:
Description:
SFR RICHT908 T19-M0084

Outstanding Activity Conditions

Permit Number - T21CM08759
Permit Status: Issued
Permit Description: SFR RICHT908 T19-M0084
Total Outstanding Activity Conditions - 1
Date Name
11/08/2021 SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED.

Completed Inspections

Permit Status: Issued
Permit Number: T21CM08759
Permit Description: SFR RICHT908 T19-M0084
Total Completed Inspections - 23
Date Description Inspector Results Comments
11/18/2021 COT - RSPL - Yard Water Line Passed {Activity date: 11/18/2021; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved}
11/18/2021 COT - RSPL - Sewer Passed {Activity date: 11/18/2021; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved}
11/18/2021 COT - RSPL - Rough Soil Passed {Activity date: 11/18/2021; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved}
11/24/2021 COT - RSEL - Grounding/Bonding Passed {Activity date: 11/24/2021; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved}
11/24/2021 COT - RSBU - Preslab Passed {Activity date: 11/24/2021; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved}
11/24/2021 COT - RSEL - Electrical Underground Passed {Activity date: 11/24/2021; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved}
11/24/2021 COT - RSBU - Excavation/Rebar/Zoning Passed {Activity date: 11/24/2021; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved}
12/21/2021 COT - RSBU - Roof Nailing Passed {Activity date: 12/21/2021; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP} ; {Activity date: 12/17/2021; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - CO.. corrections incomplete from 12/14 inspection.

} ; {Activity date: 12/14/2021; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by RSALDAT1 - CO
1. Loose sheet on southeast area.}
12/21/2021 COT - RSBU - Exterior Clips/Sheathing Passed {Activity date: 12/21/2021; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP} ; {Activity date: 12/17/2021; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - CO
None of the corrections have been made from the 12/14 inspection} ; {Activity date: 12/14/2021; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by RSALDAT1 - CO
1. Remove shims @ 2-ply girder truss mid-bearing point
2. Remove or attach loose metal bracing at top of trusses
3. Shear transfer to the roof is incomplete per detail 14/SD1.3c}
01/26/2022 PDSD Building Division - TEP PM Clearance Passed {Activity date: 01/26/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - CODE ECO}
01/26/2022 COT - RSEL - Construction Power Passed {Activity date: 01/26/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - AP
TEP ECO

}
04/19/2022 COT - LCBU - Framing Passed {Activity date: 04/19/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP}
04/19/2022 COT - RSPL - Gas Pressure Test Passed {Activity date: 04/19/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP} ; {Activity date: 04/18/2022; Status: Cancelled; Inspector: TGAUSP; Comment: Entered by VVERA1 - The following inspections are Cancelled, no response from Richmond American office
1080 (RESIDENTIAL INTERMEDIATE)
3035 (PLUMBING - INTERMEDIATE)
3050 (PLUMBING - GAS PRESSURE TEST)
4035 (MECHANICAL - INTERMEDIATE)

} ; {Activity date: 04/13/2022; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Not ready gas pressure low
}
04/25/2022 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed {Activity date: 04/25/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved} ; {Activity date: 04/22/2022; Status: Denied; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - DE
House insulated on a red tag. Remove all insulation from house.
Cancel all other inspections} ; {Activity date: 04/19/2022; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - CO.
1. Nail plate T&P line in garage
2. Burn in the line set
3. Block high/low vents in the garage
4. Repair excessive hole in roof at B-vent.
5. Secure gas line in laundry
6. Water test shower and nail plate vent above shower
7. Support both ends of 4-gang box
8. Refoam weep screed. Many gaps thruout} ; {Activity date: 04/18/2022; Status: Cancelled; Inspector: TGAUSP; Comment: Entered by VVERA1 - The following inspections are Cancelled, no response from Richmond American office
1080 (RESIDENTIAL INTERMEDIATE)
3035 (PLUMBING - INTERMEDIATE)
3050 (PLUMBING - GAS PRESSURE TEST)
4035 (MECHANICAL - INTERMEDIATE)

} ; {Activity date: 04/15/2022; Status: Not ready for Inspection; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - NR
1. Block high/low vents
2. Relieve all truss mid-point bearing points, and detach H2.5
3. Block the hammered out hole in garage shear wall.
4. Block all registers on 3 sides
INSPECTION STOPPED. THIS HOUSE IS NOT READY FOR INSPECTION

} ; {Activity date: 04/13/2022; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Not ready see 00035 results, several wires touching gussets
}
04/25/2022 COT - LCPL - Plumbing Intermediate Passed {Activity date: 04/25/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved} ; {Activity date: 04/22/2022; Status: Cancelled; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - } ; {Activity date: 04/19/2022; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - CO} ; {Activity date: 04/18/2022; Status: Cancelled; Inspector: TGAUSP; Comment: Entered by VVERA1 - The following inspections are Cancelled, no response from Richmond American office
1080 (RESIDENTIAL INTERMEDIATE)
3035 (PLUMBING - INTERMEDIATE)
3050 (PLUMBING - GAS PRESSURE TEST)
4035 (MECHANICAL - INTERMEDIATE)

} ; {Activity date: 04/13/2022; Status: Partial Approval; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Partial approval several pex lines touching metal gussets, no DWV TEST
}
04/25/2022 RSME - Mechanical Progress Passed {Activity date: 04/25/2022; Status: Approved; Inspector: ESTEVENS; Comment: Entered by NGARCIA3 - Approved} ; {Activity date: 04/22/2022; Status: Cancelled; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - } ; {Activity date: 04/19/2022; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - CO} ; {Activity date: 04/18/2022; Status: Cancelled; Inspector: TGAUSP; Comment: Entered by VVERA1 - The following inspections are Cancelled, no response from Richmond American office
1080 (RESIDENTIAL INTERMEDIATE)
3035 (PLUMBING - INTERMEDIATE)
3050 (PLUMBING - GAS PRESSURE TEST)
4035 (MECHANICAL - INTERMEDIATE)

} ; {Activity date: 04/13/2022; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Not ready installation in progress not complete

}
05/09/2022 COT - HCBU - Interior Shear Bracing Passed {Activity date: 05/09/2022; Status: Approved; Inspector: DMUNIZ; Comment: Entered by VVERA1 - Approved} ; {Activity date: 05/06/2022; Status: Correction Required; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - CO
Maintain 3/8" distance of nails/screws to edge of wallboard}
06/17/2022 COT - RSPL - Plumbing Final Passed {Activity date: 06/17/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP
SWG clearance required.}
06/17/2022 COT - BULD - SWG Clearance Passed {Activity date: 06/17/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - CODE GAS}
06/28/2022 COT - RSME - Mechanical Final Passed {Activity date: 06/28/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP}
06/28/2022 RSBU - Building Final Passed {Activity date: 06/28/2022; Status: Partial Approval; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - APPROVED BY INSPECTOR AWAITING CONDITIONS} ; {Activity date: 06/28/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP}
06/28/2022 COT - RSEL - Outdoor Lighting Passed {Activity date: 06/28/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP}
06/28/2022 COT - RSEL - Electrical Final Passed {Activity date: 06/28/2022; Status: Approved; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - AP}