Inspection Status: Passed
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 04/25/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
ESTEVENS |
Approved |
Entered by NGARCIA3 - Approved |
| 04/22/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
TLUNDBERG |
Denied |
Entered by NGARCIA3 - DE
House insulated on a red tag. Remove all insulation from house.
Cancel all other inspections |
| 04/19/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
TLUNDBERG |
Correction Required |
Entered by NGARCIA3 - CO.
1. Nail plate T&P line in garage
2. Burn in the line set
3. Block high/low vents in the garage
4. Repair excessive hole in roof at B-vent.
5. Secure gas line in laundry
6. Water test shower and nail plate vent above shower
7. Support both ends of 4-gang box
8. Refoam weep screed. Many gaps thruout |
| 04/18/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
TGAUSP |
Cancelled |
Entered by VVERA1 - The following inspections are Cancelled, no response from Richmond American office
1080 (RESIDENTIAL INTERMEDIATE)
3035 (PLUMBING - INTERMEDIATE)
3050 (PLUMBING - GAS PRESSURE TEST)
4035 (MECHANICAL - INTERMEDIATE)
|
| 04/15/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
TLUNDBERG |
Not ready for Inspection |
Entered by VVERA1 - NR
1. Block high/low vents
2. Relieve all truss mid-point bearing points, and detach H2.5
3. Block the hammered out hole in garage shear wall.
4. Block all registers on 3 sides
INSPECTION STOPPED. THIS HOUSE IS NOT READY FOR INSPECTION
|
| 04/13/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
WGALLAGHER |
Not ready for Inspection |
Entered by VVERA1 - Not ready see 00035 results, several wires touching gussets
|