Permit: T21CM00747
Permit Details
Status:
Expired
Type:
Residential Building - One or Two Family
Address:
3490 S MORMON DR
Address NEW:
3490 S MORMON DR
Apply Date:
01/26/2021
Applicant:
Description:
Installing a new electrical panel
Outstanding Inspections
Permit Status: Expired
Permit Number: T21CM00747
Permite Description: Installing a new electrical panel
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2022 | COT - RSEL - Electrical Final | N/A | Canceled | Inspection Canceled |
Completed Inspections
Permit Status: Expired
Permit Number: T21CM00747
Permit Description: Installing a new electrical panel
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2021 | PDSD Building Division - TEP PMÂ Clearance | Passed | {Activity date: 03/19/2021; Status: Approved; Inspector: WGALLAGHER; Comment: Entered by VLEON1 - CODE INCR} | |
| 03/19/2021 | COT - RSEL - Service Upgrade | Passed | {Activity date: 03/19/2021; Status: Approved; Inspector: WGALLAGHER; Comment: Entered by VLEON1 - } ; {Activity date: 03/08/2021; Status: Correction Required; Inspector: RCHANDLER; Comment: Entered by VLEON1 - CORRECTION REQUIRED - 1-Service conductors need #4 minimum ground conductor. 2-Fused conductors can not be run in the same raceway as unfused conductors. 3-Old panel is being used as a junction box; if service conductors are run through this box, it will be rendered inaccessible by TEP seal.} |