Permit: T21CM00747

Parcel: 136172640


Addresses:

3490 S MORMON DR

Inspection Status: Passed

Inspection History: COT - RSEL - Service UpgradeĀ 

Date Description Inspector Results Comments
03/19/2021 COT - RSEL - Service UpgradeĀ  WGALLAGHER Approved Entered by VLEON1 -
03/08/2021 COT - RSEL - Service UpgradeĀ  RCHANDLER Correction Required Entered by VLEON1 - CORRECTION REQUIRED - 1-Service conductors need #4 minimum ground conductor. 2-Fused conductors can not be run in the same raceway as unfused conductors. 3-Old panel is being used as a junction box; if service conductors are run through this box, it will be rendered inaccessible by TEP seal.