Inspection Status: Passed
Inspection History: COT - RSEL - Service UpgradeĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2021 |
COT - RSEL - Service UpgradeĀ |
WGALLAGHER |
Approved |
Entered by VLEON1 - |
| 03/08/2021 |
COT - RSEL - Service UpgradeĀ |
RCHANDLER |
Correction Required |
Entered by VLEON1 - CORRECTION REQUIRED - 1-Service conductors need #4 minimum ground conductor. 2-Fused conductors can not be run in the same raceway as unfused conductors. 3-Old panel is being used as a junction box; if service conductors are run through this box, it will be rendered inaccessible by TEP seal. |