Description:
BILLBOARD REPAIR

Permit Reviews

Permit Number - T21BU00498
Permit Status: Needs resubmittal
Permit Description: BILLBOARD REPAIR
Start Date Submittal Complete Date Status  
02/10/2022 BILLBOARD - BLDG30days 03/08/2022 COMPLETED Review Details
10/19/2022 BILLBOARD - BLDG30days 10/19/2022 ACTIVE Review Details
11/02/2021 BILLBOARD - BLDG30days 12/06/2021 COMPLETED Review Details
11/21/2022 PERMANENT SIGN REVIEW v.1 11/21/2022 REQUIRES RESUBMIT Review Details
04/28/2023 PERMANENT SIGN REVIEW v.2 05/11/2023 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - T21BU00498
Permit Status: Needs resubmittal
Permit Description: BILLBOARD REPAIR
Total Outstanding Activity Conditions - 1
Date Name
11/02/2021 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Needs Resubmittal
Permit Number: T21BU00498
Permite Description: BILLBOARD REPAIR
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/08/2022 COT - SIGN - Sign Final N/A Re-inspection required {Activity date: 03/08/2022; Status: Denied; Inspector: Hthrall; Comment: Entered by HTHRALL1 - Below are comments on the authorized repair resubmittal for COT ID# 592 at 10411 East Interstate 10 (T21BU00498).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. In revised 2nd paragraph of Scope of Work, correct the number of pieces and length for the 2”x6” bridge.

2. In revised 5th paragraph of Scope of Work, there is no provision for installation of new (like) second from the top stringers and bridge; please revise or clarify.

3. In 20th (last) paragraph of Scope of Work, conform the number of apron section pieces shown (9) to that shown in 16th paragraph (10) or otherwise clarify that the number of apron sections and overall width is to be reduced.

4. In revised Side View Detail, depict backrail bridge and extend existing designation for stringer bridges to this part.

Sheet 3 of 3

No comments.}