Permit Number: T21BU00498
Parcel: 305030090

Address:
10603 E I10

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T21BU00498
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2022 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair resubmittal for COT ID# 592 at 10411 East Interstate 10 (T21BU00498).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. In revised 2nd paragraph of Scope of Work, correct the number of pieces and length for the 2”x6” bridge.

2. In revised 5th paragraph of Scope of Work, there is no provision for installation of new (like) second from the top stringers and bridge; please revise or clarify.

3. In 20th (last) paragraph of Scope of Work, conform the number of apron section pieces shown (9) to that shown in 16th paragraph (10) or otherwise clarify that the number of apron sections and overall width is to be reduced.

4. In revised Side View Detail, depict backrail bridge and extend existing designation for stringer bridges to this part.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2022 NGARCIA3 OUT TO CUSTOMER Completed