Permit Details

Status:
Expired
Type:
Fire Construction Permit
Address:
1055 N PARK AV
Address NEW:
1055 N PARK AV
Apply Date:
07/08/2020
Applicant:
Description:
Automatic Fire Extingshing Sys - New Automatic Fire Sprinkler System; Commercial Fire Sprinkler Systems - Standpipe New Outlets: 17; Commercial Fire Pumps and Related Equipment - New Pumps: 1

Outstanding Inspections

Permit Status: Expired
Permit Number: T20FC00455
Permite Description: Automatic Fire Extingshing Sys - New Automatic Fire Sprinkler System; Commercial Fire Sprinkler Systems - Standpipe New Outlets: 17; Commercial Fire Pumps and Related Equipment - New Pumps: 1
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/13/2020 COT - FCON - Sprinkler - Final N/A Re-inspection required {Activity date: 08/13/2020; Status: Prior to Final Inspectn; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - * SUBJECT TO FIELD VERIFICATION
* PLEASE PRIVIDE 1 FULL SET OF DRAWINGS FOR THE JOB SITE
* PERMIT COVERS 1 FIRE PUMP INSPECTION AND 1 INSPECTION PER FLOOR AND 1 STANDPIPE TEST
* PLACARD TO BE PLACED AT FDC STATING INLET PRESSURE REQUIREMENTS FROM TFD
* FIRE PUMP TEST TO BE COORDINATED WITH TFD, TUCSON WATER AND PDSD TWO WEEKS IN ADVANCE
* IF THE FIRE PUMP TEST IS PERFORMED BEFORE 7:30 AM ADDITIONAL FEES WILL BE ADDED TO THE PERMIT CARD
* CONFIRM RISER DIAGRAMS WITH FIRE SPRINKLER CONTRACTOR FOR THE FIRE SPRINKLER GRAPHIC ANNUNCIATOR}
06/10/2021 FCON – OH Piping & Hydro N/A Canceled {Activity date: 06/10/2021; Status: Cancelled; Inspector: MRoss; Comment: Entered by MROSS2 - Inspecton cancelled by contractor} ; {Activity date: 05/28/2021; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Inspection 11 - 1st Floor A side Mezzanine. 210 psi.} ; {Activity date: 05/13/2021; Status: Partial Approval; Inspector: MRoss; Comment: Entered by MROSS2 - Inspection 10 - 6M - unit #610 missing coverage in back hallway, need to add a head.} ; {Activity date: 05/06/2021; Status: Partial Approval; Inspector: MRoss; Comment: Entered by MROSS2 - Inspection 9 - 6th floor B side - RM 623, leak in kitchen, does closet in hallway have doors ? Corrected 5-13-2021} ; {Activity date: 04/30/2021; Status: Partial Approval; Inspector: jvincent; Comment: Entered by JVINCEN1 - Inspection #6 - 6A} ; {Activity date: 04/21/2021; Status: Partial Approval; Inspector: MRoss; Comment: Entered by MROSS2 - Inspection 7 - 1st floor & mezanine B side. 215psi
-missing head in NW unit room entryway soffit.} ; {Activity date: 04/16/2021; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Inspection 6 - 5th floor, B side. 210psi.} ; {Activity date: 04/07/2021; Status: Partial Approval; Inspector: MRoss; Comment: Entered by MROSS2 - Inspection 5 - 5th floor, A side.} ; {Activity date: 03/19/2021; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Inspection 4 - 4th floor, A side. 200 psi.} ; {Activity date: 03/09/2021; Status: Partial Approval; Inspector: Mross; Comment: Entered by MROSS2 - Inspection 3 - 3rd floor buildinga A & B, residential areas. Room 308 adjust head spacing in hallway, room 302 back bedroom is missing coverage. 215 psi.} ; {Activity date: 02/18/2021; Status: Partial Approval; Inspector: MRoss; Comment: Entered by MROSS2 - Inspection 2 - 2nd floor building B, residential areas} ; {Activity date: 02/09/2021; Status: Partial Approval; Inspector: MRoss; Comment: Entered by MROSS2 - -Inspection 1 - 2nd floor, side A - residential rooms (no hallways)}

Completed Inspections

Permit Status: Expired
Permit Number: T20FC00455
Permit Description: Automatic Fire Extingshing Sys - New Automatic Fire Sprinkler System; Commercial Fire Sprinkler Systems - Standpipe New Outlets: 17; Commercial Fire Pumps and Related Equipment - New Pumps: 1
Total Completed Inspections - 3
Date Description Inspector Results Comments
06/14/2021 COT - FCON - Underground Flush Passed {Activity date: 06/14/2021; Status: Approved; Inspector: MRoss; Comment: Entered by MROSS2 - }
04/27/2021 COT - FCON - Underground Pressure Passed {Activity date: 04/27/2021; Status: Approved; Inspector: MRoss; Comment: Entered by MROSS2 - OK to backfill underground line trench}
07/28/2021 COT - FCON - Pump - Final Passed {Activity date: 07/28/2021; Status: Approved; Inspector: MRoss; Comment: Entered by MROSS2 - Fire pump test completed, verified that signals reported to panel.}