Permit Details

Status:
Expired
Type:
Fire Construction Permit
Address NEW:
2643 N CAMPBELL AV 101
Apply Date:
09/24/2019
Applicant:
Description:
Automatic Fire Extingshing Sys - HOOD FIRE SYSTEM INSTALL; Commercial Cooking Suppression - New System: 1

Outstanding Inspections

Permit Status: Expired
Permit Number: T19FC00792
Permite Description: Automatic Fire Extingshing Sys - HOOD FIRE SYSTEM INSTALL; Commercial Cooking Suppression - New System: 1
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
10/08/2019 COT - FCON - Hood System - Final N/A Partial Pass {Activity date: 10/08/2019; Status: Partial Approval; Inspector: MRoss; Comment: Entered by MROSS2 - -Submit as-built plans for changes in cookline layout} ; {Activity date: 10/04/2019; Status: Partial Approval; Inspector: jvincent; Comment: Entered by JVINCEN1 - -Provide/install/mount class K extinguisher.
-Electric behind hood did not shut off during trip test. Must shut off.
-Fryer shield x 2 required since you have burners on both sides of fryer.
-Submit revised set of hood plans. Cook lineup is different than plans.}