Permit: T19FC00792

Parcel: 11310023A

Inspection Status: Partial Pass

Inspection History: COT - FCON - Hood System - Final

Date Description Inspector Results Comments
10/08/2019 COT - FCON - Hood System - Final MRoss Partial Approval Entered by MROSS2 - -Submit as-built plans for changes in cookline layout
10/04/2019 COT - FCON - Hood System - Final jvincent Partial Approval Entered by JVINCEN1 - -Provide/install/mount class K extinguisher. -Electric behind hood did not shut off during trip test. Must shut off. -Fryer shield x 2 required since you have burners on both sides of fryer. -Submit revised set of hood plans. Cook lineup is different than plans.