Inspection Status: Partial Pass
Inspection History: COT - FCON - Hood System - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2019 |
COT - FCON - Hood System - Final |
MRoss |
Partial Approval |
Entered by MROSS2 - -Submit as-built plans for changes in cookline layout |
| 10/04/2019 |
COT - FCON - Hood System - Final |
jvincent |
Partial Approval |
Entered by JVINCEN1 - -Provide/install/mount class K extinguisher.
-Electric behind hood did not shut off during trip test. Must shut off.
-Fryer shield x 2 required since you have burners on both sides of fryer.
-Submit revised set of hood plans. Cook lineup is different than plans. |