Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
Fire Alarm & Detection Systems
Apply Date:
09/12/2019
Applicant:
ADT LLC OF DELAWARE (FN)
Description:
Installation of New Fire Alarm System
Contractors:
  • ADT LLC OF DELAWARE (FN)

Completed Inspections

Permit Status: Final
Permit Number: T19FC00740
Permit Description: Installation of New Fire Alarm System
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/18/2019 FIRE - ALARM FINAL JPEELDAVIS Approved 1) correct PIV #3
2) correct PIV #2
3) Backflow preventer shall be monitored by the fire alarm
4) Break rooms and offices need to have the notification candella match the drawings
5) Break rooms and offices shall meet minimum dBA
6) Main floor h/s shall be lowered below lights, lights raised and or photometrics provided
7) Low Voltage under 7' shall be in conduit
8) Correct the fire alarm labels and description so that they match the devices
9) FACP ROOM sign needed
10) add h/s to the vestibule area

Documents

File Name Document Type  
001_FA-0.TIF FIRE PLANS VIEW
002_FA-1.TIF FIRE PLANS VIEW
003_FA-2.TIF FIRE PLANS VIEW
004_FA-3.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW