Permit: T19FC00740
Permit Details
Apply Date:
09/12/2019
Applicant:
ADT LLC OF DELAWARE (FN)
Description:
Installation of New Fire Alarm System
Contractors:
- ADT LLC OF DELAWARE (FN)
Completed Inspections
Permit Status: Final
Permit Number: T19FC00740
Permit Description: Installation of New Fire Alarm System
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2019 | FIRE - ALARM FINAL | JPEELDAVIS | Approved | 1) correct PIV #3 2) correct PIV #2 3) Backflow preventer shall be monitored by the fire alarm 4) Break rooms and offices need to have the notification candella match the drawings 5) Break rooms and offices shall meet minimum dBA 6) Main floor h/s shall be lowered below lights, lights raised and or photometrics provided 7) Low Voltage under 7' shall be in conduit 8) Correct the fire alarm labels and description so that they match the devices 9) FACP ROOM sign needed 10) add h/s to the vestibule area |