Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T19FC00740
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2020 | FIRE - ALARM FINAL | Approved | ||
01/08/2020 | FIRE - ALARM FINAL | Partial Approval | -Provide NFPA 72 ROC paperwork -Install "FACP ROOM' sign |
|
12/18/2019 | FIRE - ALARM FINAL | Denied | 1) correct PIV #3 2) correct PIV #2 3) Backflow preventer shall be monitored by the fire alarm 4) Break rooms and offices need to have the notification candella match the drawings 5) Break rooms and offices shall meet minimum dBA 6) Main floor h/s shall be lowered below lights, lights raised and or photometrics provided 7) Low Voltage under 7' shall be in conduit 8) Correct the fire alarm labels and description so that they match the devices 9) FACP ROOM sign needed 10) add h/s to the vestibule area |