Permit: T19FC00740

Parcel: 12701008A


Addresses:

5255 E BROADWAY BL

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
01/17/2020 FIRE - ALARM FINAL Approved
01/08/2020 FIRE - ALARM FINAL Partial Approval -Provide NFPA 72 ROC paperwork
-Install "FACP ROOM' sign
12/18/2019 FIRE - ALARM FINAL Denied 1) correct PIV #3
2) correct PIV #2
3) Backflow preventer shall be monitored by the fire alarm
4) Break rooms and offices need to have the notification candella match the drawings
5) Break rooms and offices shall meet minimum dBA
6) Main floor h/s shall be lowered below lights, lights raised and or photometrics provided
7) Low Voltage under 7' shall be in conduit
8) Correct the fire alarm labels and description so that they match the devices
9) FACP ROOM sign needed
10) add h/s to the vestibule area