Permit: T19FC00659
Permit Details
Apply Date:
08/20/2019
Applicant:
HALO FIRE PROTECTION L L C
Description:
NEW FIRE SPRINKLER SYSTEM FOR NEW BUILDING
Contractors:
- HALO FIRE PROTECTION L L C
Completed Inspections
Permit Status: Final
Permit Number: T19FC00659
Permit Description: NEW FIRE SPRINKLER SYSTEM FOR NEW BUILDING
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2019 | FIRE SPKLR - OH PIPING & HYDRO | MRoss | Approved | Submit as-built plans prior to final inspection |
12/17/2019 | FIRE SPKLR - FINAL | JPEELDAVIS | Approved | 1) PIV #3 tamper switch shall be replaced 2) PIV #2 tamper switch shall be replaced 3) heads in the vestibule are painted and shall be replaced. Provide TFD with the painted heads 4) Remove existing demoed watermotor gong 5) Fire sprinkler drawings need to be revised and re-submitted to TFD 6) Double backflow preventer shall be monitored |