Permit: T19FC00659

Parcel: 12701008A


Addresses:

5255 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T19FC00659

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2020 FIRE SPKLR - FINAL Approved
01/09/2020 FIRE SPKLR - FINAL Partial Approval Ok for TCO to stock merchandise

1. Submit as-built plans
2. Replace painted spare heads in riser room 2
3. Install supply side pressure guages
4. Provide verification that existing FDC works properly
12/17/2019 FIRE SPKLR - FINAL Partial Approval 1) PIV #3 tamper switch shall be replaced
2) PIV #2 tamper switch shall be replaced
3) heads in the vestibule are painted and shall be replaced. Provide TFD with the painted heads
4) Remove existing demoed watermotor gong
5) Fire sprinkler drawings need to be revised and re-submitted to TFD
6) Double backflow preventer shall be monitored