Status:
Final
Type:
Fire Alarm & Detection Systems
Address:
300 W WETMORE RD
Address NEW:
300 W WETMORE RD
Apply Date:
07/23/2019
Applicant:
JOHNSON CONTROLS INC ,
Description:
Upgrade existing Fire Alarm System
Contractors:
  • JOHNSON CONTROLS INC ,

Completed Inspections

Permit Status: Final
Permit Number: T19FC00569
Permit Description: Upgrade existing Fire Alarm System
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/05/2019 FIRE - ALARM FINAL JPEELDAVIS Approved 1) Circuit breaker shall be RED lock out that reads FIRE ALARM
2) Ansul system shall report as an alarm
3) Need to test and verify the CO system
4) Need to add notification device in wak in cooler per approved plan
5) Monitoring shall have 1 phone line and cell
6) Cell transformer shall be in a locked enclosure
7) tamper switch shall unlatch as a supervisory and shall not set off the fire sprinkler bell