Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2020 | FIRE - ALARM FINAL | Approved | ||
| 03/06/2020 | FIRE - ALARM FINAL | Denied | fire sprinkler bell does not work when waterflow is operated. correct the issue and pay re-inspection fees prior to calling final back in | |
| 02/28/2020 | FIRE - ALARM FINAL | Cancelled | IVRS - RI canceled | |
| 01/31/2020 | FIRE - ALARM FINAL | Denied | PRETEST, PRETEST, PRETEST. -Tamper switch needs to be supervisory. Cannot be a general alarm, cannot be a trouble, cannot initiate the horn/strobes. -Need to test CO2 alarm zones. -Reinspection fee added to permit. Must be paid prior to next inspection. |
|
| 12/05/2019 | FIRE - ALARM FINAL | Partial Approval | 1) Circuit breaker shall be RED lock out that reads FIRE ALARM 2) Ansul system shall report as an alarm 3) Need to test and verify the CO system 4) Need to add notification device in wak in cooler per approved plan 5) Monitoring shall have 1 phone line and cell 6) Cell transformer shall be in a locked enclosure 7) tamper switch shall unlatch as a supervisory and shall not set off the fire sprinkler bell |