Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
Automatic Fire Extingshing Sys
Address:
4984 E 22ND ST
Address NEW:
4984 E 22ND ST
Apply Date:
02/27/2019
Applicant:
NAVARRETE FIRE PROTECTION LLC
Description:
(PHASE 1) NEW FIRE SPRINKLER SYSTEM- ALSO INCLUDE 4' UNDERGROUND FIRELINE FOR PERMIT.
Contractors:
  • NAVARRETE FIRE PROTECTION LLC

Completed Inspections

Permit Status: Final
Permit Number: T19FC00154
Permit Description: (PHASE 1) NEW FIRE SPRINKLER SYSTEM- ALSO INCLUDE 4' UNDERGROUND FIRELINE FOR PERMIT.
Total Completed Inspections - 4
Date Description Inspector Results Comments
03/25/2019 FIRE SPKLR - UG, PIPING, HYDRO MRoss Approved
05/14/2019 FIRE SPKLR - UG PIPING FLUSH MRoss Approved
05/30/2019 FIRE SPKLR - OH PIPING & HYDRO MRoss Approved Partial approval for 2nd floor. ok to install droped ceilings.
Heads obstructed by ductwork, add heads at these locations.
1. north side of stairwell
2. 2 heads on east side of hallway
3. in mens restroom
4. in office
5. in breakroom

These heads can be verified at time of final inspection
08/24/2021 FIRE SPKLR - FINAL MRoss Approved

Documents

File Name Document Type  
001_FP-1.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW