Permit: T19FC00154

Parcel: 131010400


Addresses:

4984 E 22ND ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
02/03/2020 FIRE SPKLR - OH PIPING & HYDRO Approved
05/30/2019 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Partial approval for 2nd floor. ok to install droped ceilings.
Heads obstructed by ductwork, add heads at these locations.
1. north side of stairwell
2. 2 heads on east side of hallway
3. in mens restroom
4. in office
5. in breakroom

These heads can be verified at time of final inspection
05/28/2019 FIRE SPKLR - OH PIPING & HYDRO Cancelled IVRS - RI canceled
03/05/2019 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Partial inspection 1 of 3. First floor only.

- Provide As-Built plans for changes to piping
-Verify allowable volume of concealed combustible areas
-Combustible stairs need to be covered with non combustible materials or have sprinkler coverage.