Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2020 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 05/30/2019 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Partial approval for 2nd floor. ok to install droped ceilings. Heads obstructed by ductwork, add heads at these locations. 1. north side of stairwell 2. 2 heads on east side of hallway 3. in mens restroom 4. in office 5. in breakroom These heads can be verified at time of final inspection |
|
| 05/28/2019 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | IVRS - RI canceled | |
| 03/05/2019 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Partial inspection 1 of 3. First floor only. - Provide As-Built plans for changes to piping -Verify allowable volume of concealed combustible areas -Combustible stairs need to be covered with non combustible materials or have sprinkler coverage. |