Permit Details

Status:
Final
Type:
Automatic Fire Extingshing Sys
Address NEW:
3950 E IRVINGTON RD
Apply Date:
01/17/2019
Applicant:
KAZAL FIRE PROTECTION INC
Description:
INSTAKK NEW WET PIPE FIRE SPRINKLER SYSTEM.
Contractors:
  • KAZAL FIRE PROTECTION INC

Completed Inspections

Permit Status: Final
Permit Number: T19FC00051
Permit Description: INSTAKK NEW WET PIPE FIRE SPRINKLER SYSTEM.
Total Completed Inspections - 2
Date Description Inspector Results Comments
07/10/2019 FIRE SPKLR - OH PIPING & HYDRO JPEELDAVIS Approved East Riser @ 220 psi
Middle Riser @ 220 psi
West Riser @ 210 psi
Shall add heads under obstructions over 48" throughout the facility
1 line needs to be rotated slightly
One line needs to be lowered so that the structural straps are not touching the fire sprinkler head
11/20/2019 FIRE SPKLR - FINAL JPEELDAVIS Approved All items completed 11/20/2019