Permit: T19FC00051

Parcel: 14002010A


Addresses:

3950 E IRVINGTON RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
07/10/2019 FIRE SPKLR - OH PIPING & HYDRO Approved East Riser @ 220 psi
Middle Riser @ 220 psi
West Riser @ 210 psi
Shall add heads under obstructions over 48" throughout the facility
1 line needs to be rotated slightly
One line needs to be lowered so that the structural straps are not touching the fire sprinkler head