Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2019 | FIRE SPKLR - OH PIPING & HYDRO | Approved | East Riser @ 220 psi Middle Riser @ 220 psi West Riser @ 210 psi Shall add heads under obstructions over 48" throughout the facility 1 line needs to be rotated slightly One line needs to be lowered so that the structural straps are not touching the fire sprinkler head |