Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T19CM06689
Permit Details
Apply Date:
09/13/2019
Applicant:
FRANK ANZALDUA -SOLON CORPORATION
Description:
PV PARKING SHADE CANOPIES
Contractors:
- SOLON CORPORATION
- SOLON CORPORATION ***APA***
Permit Reviews
Permit Number - T19CM06689
Permit Status: L of c
Permit Description: PV PARKING SHADE CANOPIES
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/13/2019 | PLANS OK TO SUBMIT - COMM | 09/13/2019 | COMPLETED |
09/13/2019 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 10/17/2019 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T19CM06689
Permit Status: L of c
Permit Description: PV PARKING SHADE CANOPIES
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/13/2019 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: L of c
Permit Number: T19CM06689
Permit Description: PV PARKING SHADE CANOPIES
Total Completed Inspections - 10
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2019 | ELECTRIC - UFER | TVALENCIA | Approved | 1- columns B and C hole depth is okay and Ufer conductor provided. |
10/24/2019 | EXCAVATION/LAYOUT REBAR & ZON | TVALENCIA | Approved | 1- columns B and C hole depth is okay and Ufer conductor provided. |
11/07/2019 | ELECTRIC - UNDERGROUND | TVALENCIA | Approved | 1- Underground electric conduits are okay to cover from AC disconnect to pull box and from pull box to SES and from pull box to the curb towards Canopy A only. |
11/14/2019 | FRAMING | ESTEVENS | Approved | Canopies B&C. |
12/11/2019 | TEP CLEARANCE - PM | DMUNIZ | Approved | CODE RECN/DGL |
12/11/2019 | ELECTRIC - RECONNECT | DMUNIZ | Approved | Inspection for Interconnection of phase 1 PV system, from Disconnect #2 to Existing 600AMP 480/277V SES. Parallel #350MCM Ungrounded Conductors, Parallel #1AWG Grnd/Neutral. Interconnection on Existing lugs, no modifications done to SES. Verbal Clearance sent to TEP @ 7:05AM (RECN/DGL). |
02/12/2020 | ENGINEERING - FINAL | BBENEDON | Approved | |
02/12/2020 | ELECTRIC - FINAL | TVALENCIA | Approved | Clear electric DGC |
02/12/2020 | ELECTRIC - OUTDOOR LIGHTING | TVALENCIA | Approved | |
02/14/2020 | BUILDING - FINAL | TVALENCIA | Approved |