Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
L of c
Type:
COMMERCIAL OTHER
Address NEW:
1310 W MIRACLE MILE
Apply Date:
04/11/2019
Applicant:
SOLON CORPORATION ***APA***
Description:
PV SHADE CANOPIES
Contractors:
  • SOLON CORPORATION ***APA***

Permit Reviews

Permit Number - T19CM02540
Permit Status: L of c
Permit Description: PV SHADE CANOPIES
Start Date Submittal Complete Date Status  
04/11/2019 PLANS OK TO SUBMIT - COMM 04/11/2019 COMPLETED Review Details
04/11/2019 COMMERCIAL - TI 05/10/2019 COMPLETED Review Details
05/10/2019 RESUBMITTAL 05/10/2019 COMPLETED Review Details

Completed Inspections

Permit Status: L of c
Permit Number: T19CM02540
Permit Description: PV SHADE CANOPIES
Total Completed Inspections - 11
Date Description Inspector Results Comments
05/30/2019 EXCAVATION/LAYOUT REBAR & ZON TVALENCIA Approved
06/07/2019 ELECTRIC - UNDERGROUND TVALENCIA Approved 1- Underground electric conduits from Array A to the main service panel and from the service panel west to the service road to the transformer is okay to cover.
07/08/2019 ELECTRIC - UFER RCAMACHO Approved
07/08/2019 ELECTRIC - INTERMEDIATE RCAMACHO Approved
07/08/2019 ELECTRIC - PROGRESS RCAMACHO Approved
09/21/2019 ELECTRIC - RECONNECT DMUNIZ Approved Inspection for Interconnection of PV System.
2 Sets of #600KCMIL Conductors, 2/0Neutral, 2/0Ground.
277/480V (700AMP) Shunt Breaker to CT Can.
CT Can to 700AMP PV Utility Disconnect.
Disconnect to Existing Square D 3000AMP SES, Line side Tap Approved.
Third party on site to provide Hi-pot & Re-Certify Gear.
Verbal Clearance sent to TEP @ 10:30AM (RECN).
Please Clear (DGL).
09/23/2019 TEP CLEARANCE - PM DMUNIZ Approved CODE RECN/DGL
Clear dgl and dgc for phase 1. Meter box M - 01
09/23/2019 ELECTRIC - FINAL DQUINN Approved Clear dgl and dgc for phase 1. Meter box M - 01
09/23/2019 OUTDOOR LIGHTING FINAL DQUINN Approved
09/23/2019 ELECTRIC - OUTDOOR LIGHTING DQUINN Approved
09/23/2019 BUILDING - FINAL DQUINN Approved

Documents

File Name Document Type  
None LETTER OF COMPLETION VIEW