Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T19CM02540

Parcel: 10706013E


Addresses:

1310 W MIRACLE MILE

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/21/2019 ELECTRIC - RECONNECT Approved Inspection for Interconnection of PV System.
2 Sets of #600KCMIL Conductors, 2/0Neutral, 2/0Ground.
277/480V (700AMP) Shunt Breaker to CT Can.
CT Can to 700AMP PV Utility Disconnect.
Disconnect to Existing Square D 3000AMP SES, Line side Tap Approved.
Third party on site to provide Hi-pot & Re-Certify Gear.
Verbal Clearance sent to TEP @ 10:30AM (RECN).
Please Clear (DGL).