Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2019 | ELECTRIC - RECONNECT | Approved | Inspection for Interconnection of PV System. 2 Sets of #600KCMIL Conductors, 2/0Neutral, 2/0Ground. 277/480V (700AMP) Shunt Breaker to CT Can. CT Can to 700AMP PV Utility Disconnect. Disconnect to Existing Square D 3000AMP SES, Line side Tap Approved. Third party on site to provide Hi-pot & Re-Certify Gear. Verbal Clearance sent to TEP @ 10:30AM (RECN). Please Clear (DGL). |