Permit: T19CM01385
Permit Details
Apply Date:
02/26/2019
Applicant:
VICTOR BOLDUC
Description:
LAND LORD DEMIZING WALL
Contractors:
- BJERK BUILDERS INC
Permit Reviews
Permit Number - T19CM01385
Permit Status: Final
Permit Description: LAND LORD DEMIZING WALL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
02/26/2019 | COMMERCIAL - TI | 02/26/2019 | ACTIVE |
Outstanding Activity Conditions
Permit Number - T19CM01385
Permit Status: Final
Permit Description: LAND LORD DEMIZING WALL
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
02/26/2019 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T19CM01385
Permit Description: LAND LORD DEMIZING WALL
Total Completed Inspections - 15
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2019 | FRAMING | MHASSAN | Approved | |
04/25/2019 | ELECTRIC - SERVICE UPGRADE | BSTEVENS | Approved | THIS WAS FOR THE ADDITION OF A 600 A SERVICE TO SEPERATE THE SUITES |
04/25/2019 | TEP CLEARANCE - PM | BSTEVENS | Approved | CODE INCR |
04/25/2019 | ELECTRIC - FINAL | BSTEVENS | Approved | Clear INCR |
05/01/2019 | FIREWALL/FIREBARRIER/FIRESTOP | RCAMACHO | Approved | See letterhead from architect of record Thomas Sayler Brown per details two and three on sheet aA1.0 calls for fire caulk. It is acceptable to use acoustical sealant instead , since the demising wall is not required to be fire rated for M occupancy. No separation is required. Contractor made hole in Sheetrock to verify 2 layers of 5/8” Sheetrock each side |
05/01/2019 | PLUMBING - FINAL | RCAMACHO | Approved | |
05/01/2019 | PLUMBING - INTERMEDIATE | RCAMACHO | Approved | |
05/01/2019 | ELECTRIC - UNDERGROUND | RCAMACHO | Approved | |
05/01/2019 | ELECTRIC - ABOVE CEILING | RCAMACHO | Approved | |
05/01/2019 | ELECTRIC - INTERMEDIATE | RCAMACHO | Approved | |
05/01/2019 | BUILDING ABOVE CEILING | RCAMACHO | Approved | |
05/02/2019 | FIRE - FINAL | gsereno1 | Approved | |
05/02/2019 | ENGINEERING - FINAL | BBENEDON | Approved | |
05/08/2019 | FIRE SPKLR - FINAL | CBASALDUA | Approved | |
05/14/2019 | BUILDING - FINAL | RCAMACHO | Approved |