Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
3809 E 3RD ST
Address NEW:
3809 E 3RD ST
Apply Date:
02/25/2019
Applicant:
TECHNICIANS FOR SUSTAINABILITY INC
Description:
PV PARKING CANOPY
Contractors:
  • TECHNICIANS FOR SUSTAINABILITY INC

Permit Reviews

Permit Number - T19CM01343
Permit Status: Final
Permit Description: PV PARKING CANOPY
Start Date Submittal Complete Date Status  
02/25/2019 COMMERCIAL - BLDG/FIRE/ZONING/ENG 02/25/2019 COMPLETED Review Details
02/25/2019 COMMERCIAL - BLDG/FIRE/ZONING/ENG 03/26/2019 COMPLETED Review Details
03/26/2019 REVISION - - 1ST 03/26/2019 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T19CM01343
Permit Status: Final
Permit Description: PV PARKING CANOPY
Total Outstanding Activity Conditions - 1
Date Name
02/25/2019 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T19CM01343
Permit Description: PV PARKING CANOPY
Total Completed Inspections - 9
Date Description Inspector Results Comments
04/04/2019 ELECTRIC - UNDERGROUND BSTEVENS Approved
05/11/2019 ELECTRIC - RECONNECT DMUNIZ Approved (DGL)
125KVA Transformer to 1200AMP CT Cabinet.
CT Cabinet to 400 AMP Utility Disconnect.
Disconnect to Interconnection of Existing 1200AMP SES.
3/0 Parallel Conductors, 2-2" Conduits, #4 Neutral/ #4 Ground.
Third party on site to Re-certify Gear.
TEP Verbal Clearance sent at 11:30AM (DGL)
05/13/2019 TEP CLEARANCE - AM BSTEVENS Approved CODE DGL/DGC
05/13/2019 ELECTRIC - FINAL BSTEVENS Approved
05/13/2019 ELECTRIC - UFER BSTEVENS Approved
05/13/2019 BUILDING - FINAL BSTEVENS Approved
05/13/2019 FRAMING BSTEVENS Approved
05/13/2019 EXCAVATION/LAYOUT REBAR & ZON BSTEVENS Approved
05/13/2019 TEP CLEARANCE - PM DMUNIZ Approved CODE DGL