Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
200 S ALVERNON WY
Apply Date:
02/21/2019
Applicant:
SOLON CORPORATION ***APA***
Description:
PV SHADE CANOPIES
Contractors:
  • SOLON CORPORATION ***APA***

Permit Reviews

Permit Number - T19CM01283
Permit Status: Final
Permit Description: PV SHADE CANOPIES
Start Date Submittal Complete Date Status  
02/21/2019 COMMERCIAL - BLDG/FIRE/ZONING/ENG 03/20/2019 ACTIVE Review Details
02/21/2019 COMMERCIAL - BLDG/FIRE/ZONING/ENG 02/21/2019 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T19CM01283
Permit Status: Final
Permit Description: PV SHADE CANOPIES
Total Outstanding Activity Conditions - 1
Date Name
02/21/2019 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T19CM01283
Permit Description: PV SHADE CANOPIES
Total Completed Inspections - 11
Date Description Inspector Results Comments
05/09/2019 EXCAVATION/LAYOUT REBAR & ZON GWEST Approved 2x13 footings for 19 park and shade supports. 3 Ufers 20 wrapped
05/09/2019 ELECTRIC - UFER GWEST Approved 2x13 footings for 19 park and shade supports. 3 Ufers 20 wrapped
05/10/2019 ELECTRIC - UNDERGROUND RCHANDLER Approved
05/22/2019 ELECTRIC - INTERMEDIATE DQUINN Approved
05/22/2019 FRAMING DQUINN Approved
06/09/2019 ELECTRIC - RECONNECT DMUNIZ Approved Re-location and installation of 1200 AMP CT Meter Cabinet, New Sets of Parallel #500 MCM Conductors from Existing 120/208V Transformer to new CT Cabinet ok.
New (2) sets of Parallel #600 MCM Conductors from New CT to Existing 800AMP SES OK, LINE Side Tap Approved .System Grounded and bonded Per NEC.
Sent Verbal Clearance @ 10:45pm (RECN/DGL). Contractor to call in another inspection for Finals, Utility Disconnects not finished and to still be inspected prior to release of a Solar Meter (DGC).
$165 Check received upon arrival of inspection (AFTERHOURS)
06/11/2019 BUILDING - FINAL GWEST Approved ALL COT REQUIREMENTS COMPLETE
06/11/2019 OUTDOOR LIGHTING FINAL GWEST Approved
06/11/2019 BUILDING - FINAL GWEST Approved Approved upon meeting all COT requirements and other department approvals and sign offs.
07/22/2019 ELECTRIC - FINAL DMUNIZ Approved Clear TEP (DGC) for 200 S Alvernon, ok to close this permit.
Verbal Clearance sent in for 202 S Alvernon @ 7:59 PM (RECN).
Check for $165 received upon arrival.
08/22/2019 TEP CLEARANCE - PM AQUIROZ Approved TEPDG -13856 CODE DGC